SKIM500W Insulation Monitoring for Wind Turbine

SKIM500W Insulation Monitoring for Wind Turbine

Offline insulation monitor specially designed for wind turbines.
Description
Sikcon's SKIM500W is an insulation monitoring device specially designed for wind turbines, which is an offline insulation monitoring device to measure the insulation of cables or turbine windings, etc. The test voltage is DC500V, and the device is interlocked with the wind turbine circuit for control. It automatically realizes the disconnection of the insulation monitoring instrument from the power grid when the generator is running. When the generator is shut down, the insulation monitoring instrument automatically starts to detect the insulation between the generator stator winding to ground, rotor winding to ground, and stator winding to rotor winding. This product can effectively eliminate the cost and safety risks of manual measurement with a megohmmeter.

SKIM500W Features
1. Suitable for wind turbines below 1140V;
2. Conduct insulation testing on the three circuits of the generator stator winding to ground, rotor winding to ground, and stator winding to rotor winding;
3. Three independent relay alarm outputs;
4. Testing and resetting functions;
5. LCD screen with backlight display, which can view and set various parameters;
6. RS-485 interface communication, using Modbus protocol, can communicate with remote upper computer;
7. The measurement process is fully automatic and can also be manually turned on;
8. Measurement protection function to protect the safe operation of equipment during measurement;
9. Leakage protection

SKIM500W Technical Data Download

SKIM500W Specification
Items Value
Power Supply AC 85~265V, 50Hz
Rated Power <5W
Insulation Resistance Measurement Range 0~500 MΩ
Insulation Alarm Set 0~99 MΩ
Insulation Warning Set 0~99 MΩ
Minimum Resolution 10kΩ
Measure Voltage DC500V
Measure Internal Resistance 400 kΩ
Dry Contact Output Normally Closed Contact, 250VAC/6A; 30V/6A
Weight ≤0.6KG
Size 135x89x110mm


SKIM500W Dimensions

SKIM500W Connection

 

 

 

 

Focusing on production and sales of insulation monitoring, insulation fault locator, residual current monitor etc.
Focusing on production and sales of insulation monitoring, insulation fault locator, residual current monitor etc.

Email:info@sikcon.com