SKIM600M Insulation Monitoring Device
SKIM600M is an insulation monitoring device for IT system main circuits and control circuits below AC690V and DC400V. SKIM600M can only perform insulation monitoring independently (the wiring method can only be used at the AC end) and cannot be combined with the insulation fault location.
Insulation Monitoring Device for IT system
Model* |
SKIM200 |
SKIM400 |
SKIM600M |
SKIM600FL |
SKIM600H |
Main circuits |
X |
√ |
√ |
√ |
√ |
Control circuits |
√ |
√ |
√ |
√ |
√ |
DC |
- |
400V |
400V |
400V |
- |
AC |
230V |
400V |
690V |
690V |
1140V |
DC/AC |
230V |
400V/400V |
400V/690V |
400V/690V |
1140V |
IFL system |
X |
X |
X |
√ |
X |
Note: Sikcon can customize insulation monitoring products with different voltages and functions according to customer needs.
SKIM600M Feature:
1. Applicable to IT systems main circuits and control circuits systems below AC690 and DC 400V;
2. Internal/external testing/reset buttons;
3. Automatic and manual reset functions;
4. Multi type, wide range control power input;
5. Humanized and easy to operate interface, which can display various parameters and system leakage capacitance;
6. DIN rail installation method;
7. LCD screen display with backlight;
8. Measure and display the insulation resistance of ungrounded systems;
9. Measurement and display of leakage capacitance (C);
10. Communication via Modbus RS-485;
11. Adjustable response delay;
12. Two independent alarm relays (each relay has a switching contact);
13. N/O or N/C operation (optional).
SKIM600M Insulation Monitor Technical Data Download
SKIM600M Technical Data
Item |
Value |
IT system Rated Voltage |
AV690V, DC400V |
Rated Power |
≤4kW |
Alarm Value Ran 1 |
1 ~9999 kΩ |
Alarm Value Ran 2 |
1 ~9999 kΩ |
Response time at R=0.5xRan and G=1 μ F |
≤4s |
Insulation Alarm Delay |
0…9999s |
Measure Voltage(U1) |
士60V |
Internal Resistance (R1) |
≥152 kΩ |
Measurement Accuracy(1~5 kΩ) |
士1 kΩ |
Measurement Accuracy(5 kΩ~1MΩ) |
+15 % |
Permissible Leakage Capacitance (Ce) |
≤ 200 μF |
Positioning Voltage |
士90V |
Positioning Current |
<4.5mA |
Response time (Fault Location) |
<30s |
SKIFL12 Accessible quantity |
≤16 |