SKIM600M  Insulation Monitoring Device

SKIM600M Insulation Monitoring Device

Main circuits and control circuits of IT system below AC690V and AC/DC690V
Description
SKIM600M Insulation Monitoring Device
SKIM600M is an insulation monitoring device for IT system main circuits and control circuits below AC690V and DC400V. SKIM600M can only perform insulation monitoring independently (the wiring method can only be used at the AC end) and cannot be combined with the insulation fault location.

Insulation Monitoring Device for IT system
 
Model* SKIM200 SKIM400 SKIM600M SKIM600FL SKIM600H
Main circuits X
Control circuits
DC - 400V 400V 400V -
AC 230V 400V 690V 690V 1140V
DC/AC 230V 400V/400V 400V/690V 400V/690V 1140V
IFL system X X X X










Note: Sikcon can customize insulation monitoring products with different voltages and functions according to customer needs.

SKIM600M Feature:
1. Applicable to IT systems main circuits and control circuits systems below AC690 and DC 400V;
2. Internal/external testing/reset buttons;
3. Automatic and manual reset functions;
4. Multi type, wide range control power input;
5. Humanized and easy to operate interface, which can display various parameters and system leakage capacitance;
6. DIN rail installation method;
7. LCD screen display with backlight;
8. Measure and display the insulation resistance of ungrounded systems;
9. Measurement and display of leakage capacitance (C);
10. Communication via Modbus RS-485;
11. Adjustable response delay;
12. Two independent alarm relays (each relay has a switching contact);
13. N/O or N/C operation (optional).

SKIM600M Insulation Monitor Technical Data Download

SKIM600M Technical Data
Item Value
IT system Rated Voltage AV690V, DC400V
Rated Power ≤4kW
Alarm Value Ran 1 1 ~9999 kΩ
Alarm Value Ran 2 1 ~9999 kΩ
Response time at R=0.5xRan and G=1 μ F ≤4s
Insulation Alarm Delay 0…9999s
Measure Voltage(U1) 士60V
Internal Resistance (R1) ≥152 kΩ
Measurement Accuracy(1~5 kΩ) 士1 kΩ
Measurement Accuracy(5 kΩ~1MΩ) +15 %
Permissible Leakage Capacitance (Ce) ≤ 200 μF
Positioning Voltage 士90V
Positioning Current <4.5mA
Response time (Fault Location) <30s
SKIFL12 Accessible quantity ≤16

 

 

Focusing on production and sales of insulation monitoring, insulation fault locator, residual current monitor etc.
Focusing on production and sales of insulation monitoring, insulation fault locator, residual current monitor etc.

Email:info@sikcon.com

Address:Guangzhou, Guangdong Province, China