SKIM200 is an insulation monitoring device for IT system control circuits below AC, and AC/DC 230V. SKIM200 can only perform insulation monitoring independently and cannot be combined with the insulation fault location.
SKIM200 Insulation monitor features:
1. Applicable to IT systems control circuits below AC/DC 230V;
2. Internal/external testing/reset buttons;
3. Automatic and manual reset functions;
4. Multi type, wide range control power input;
5. Humanized and easy to operate interface, which can display various parameters and system leakage capacitance;
6. DIN rail installation method;
7. LCD screen display with backlight;
8. Measure and display the insulation resistance of ungrounded systems;
9. Measurement and display of leakage capacitance (C);
10. Communication via Modbus RS-485;
11. Adjustable response delay;
12. Two independent alarm relays (each relay has a switching contact);
13. N/O or N/C operation (optional).
Insulation Monitoring Device for IT system
Model* |
SKIM200 |
SKIM400 |
SKIM600M |
SKIM600FL |
SKIM600H |
Main circuits |
X |
√ |
√ |
√ |
√ |
Control circuits |
√ |
√ |
√ |
√ |
√ |
DC |
- |
400V |
400V |
400V |
- |
AC |
230V |
400V |
690V |
690V |
1140V |
DC/AC |
230V |
400V/400V |
400V/690V |
400V/690V |
1140V |
IFL system |
X |
X |
X |
√ |
X |
Note: Sikcon can customize insulation monitoring products with different voltages and functions according to customer needs.
SKIM200 Insulation Monitoring Device Technical Data Download
SKIM200 Specification
Item |
Value |
IT system Rated Voltage |
≤230V |
Power supply |
AC 85-265V, DC18-36V |
Alarm Value Ran 1 |
1…9999 kΩ |
Response time at R=0.5xRan and G=1 μ F |
≤4s |
Insulation Alarm Delay |
0…9999s |
Measure Voltage(U1) |
24V |
Internal Resistance (R1) |
≥120 kΩ |
Resistance Measurement Range |
1kΩ~20MΩ |
Resistance Measurement Range |
1kΩ~20MΩ |
Measurement Accuracy(1~5 kΩ) |
士1 kΩ |
Measurement Accuracy(5 kΩ~1MΩ) |
+15 % |
+15 %Permissible Leakage Capacitance (Ce) |
≤ 200 μF(Distributed capacitance curve in the manual) |